However, when
Phase mode
is "Three Phase", all the monitored phase signal magnitudes,
defined with
Phase supervision
, have to fall below or rise above the limit setting to
activate the
PICKUP
output and the corresponding phase output, that is, all the monitored
phases have to be activated. Accordingly, the deactivation occurs when the activation
requirement is not fulfilled, that is, one or more monitored phase signal magnitudes return
beyond their limits. Phases do not need to be activated by the same variation type to
activate the
PICKUP
output. Another consequence is that if only one or two phases are
monitored, it is sufficient that these monitored phases activate the
PICKUP
output.
8.3.4.2
Variation detection
The module compares the measured voltage against the limit settings. If there is a
permanent undervoltage or overvoltage, the
Reference voltage
setting can be set to this
voltage level to avoid the undesired voltage dip or swell indications. This is accomplished
by converting the variation limits with the
Reference voltage
setting in the variation
detection module, that is, when there is a voltage different from the nominal voltage, the
Reference voltage
setting is set to this voltage.
The
Variation enable
setting is used for enabling or disabling the variation types. By
default, the setting value is "Swell+dip+Int" and all the alternative variation types are
indicated. For example, for setting "Swell+dip", the interruption detection is not active
and only swell or dip events are indicated.
In a case where
Phase mode
is "Single Phase" and the dip functionality is available, the
output
DIPST
is activated when the measured TRMS value drops below the
Voltage dip
set 3
setting in one phase and also remains above the
Voltage Int set
setting. If the voltage
drops below the
Voltage Int set
setting, the output
INTST
is activated.
INTST
is
deactivated when the voltage value rises above the setting
Voltage Int set
. When the same
measured TRMS magnitude rises above the setting
Voltage swell set 3
, the
SWELLST
output is activated.
There are three setting value limits for dip (
Voltage dip set 1..3
) and swell activation
(
Voltage swell set 1..3
) and one setting value limit for interruption.
If
Phase mode
is "Three Phase", the
DIPST
and
INTST
outputs are
activated when the voltage levels of all monitored phases, defined with the
parameter
Phase supervision
, drop below the
Voltage Int set
setting value.
An example for the detection principle of voltage interruption for "Three
Phase" when
Phase supervision
is "Ph A + B + C", and also the
corresponding pickup signals when
Phase mode
is "Single Phase", are as
shown in the example for the detection of a three-phase interruption.
Section 8
1MRS240050-IB C
Power quality measurement functions
422
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...