I
I
k I
ZL
ZL
ZL
rly
rly
Zero
Pos
Pos
*
*
* (
) /
=
+
−
0
GUID-DC024A67-96A6-42A0-A9CC-1D814F9CA607 V1 EN
(Equation 31)
where
I
I
A
I
B
I
C
0
3
=
+
+
( _
_
_
) /
GUID-522CAF08-239C-4194-89BD-FC39A043568D V1 EN
(Equation 32)
k
1.0 (scaling factor)
ZL
pos
and ZL
zero
refer to positive and zero-sequence line impedances.
ZL
pos
RL
pos
+ j*XL
pos
ZL
zero
RL
zero
+ j*XL
zero
RL
pos
PosSeqR * LinLen
XL
pos
PosSeqX * LinLen
RL
zero
ZeroSeqR * LinLen
XL
zero
ZeroSeqX * LinLen
I*
rly
Ground-compensated phase current
I
rly
Non-compensated phase current
R1
is positive-sequence line resistance in ohm/(miles or Kms) and is provided as a setting
X1
is positive-sequence line reactance in ohm/(miles or Kms) and is provided as a setting
R0
is zero-sequence line resistance in ohm/(miles or Kms) and is provided as a setting
X0
is zero-sequence line reactance in ohm/(miles or Kms) and is provided as a setting
Line Length
is the length of the line in the units of Km (kilometers) or miles and is provided
as a setting.
If
R1
,
X1
,
R0
,
X0
are given in ohm/mile, the length of the line
Line Length
should be given
in the unit of miles
If
R1
,
X1
,
R0
,
X0
are given in ohm/Km, the length of the line
Line Length
should be given
in the unit of Km.
describes what are the voltage phasor and current phasor under different fault
types.
1MRS240050-IB C
Section 10
Recording functions
REF615R
529
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...