4.2.5.10
Technical data
Table 206:
24 Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the voltage
measured: f
n
±2 Hz
±2.5% of the set value or 0.01 × Ub/f
Pickup time
1)2)
Frequency change
Typically 200 ms (±20
ms)
Voltage change
Typically 100 ms (±20
ms)
Reset time
<60 ms
Reset ratio
Typically 0.96
Retardation time
<45 ms
Operate time accuracy in definite-time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse-time mode
±5.0% of the theoretical value or ±50 ms
1) Results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
4.3
Frequency protection
4.3.1
Frequency protection 81
4.3.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Frequency protection
FRPFRQ
f>/f<,df/dt
81
4.3.1.2
Function block
81
F
PICKUP
PICKUP_UFRQ
BLOCK
PICKUP_OFRQ
PICKUP_FRG
TRIP
TRIP_UFRQ
TRIP_OFRQ
TRIP_FRG
dF/dt
GUID-8B7AA565-288B-42EA-961B-A9F7B93E47F0-ANSI V3 EN
Figure 125:
Function block
1MRS240050-IB C
Section 4
Protection functions
REF615R
263
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...