PQSS contains a blocking functionality. It is possible to block a set of function outputs or
the function itself, if desired.
8.3.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of PQSS can be described with a module diagram. All the modules in the
diagram are explained in the next sections.
GUID-91ED3E3D-F014-49EE-B4B0-DAD2509DD013-ANSI V1 EN
Figure 218:
Functional module diagram
8.3.4.1
Phase mode setting
PQSS is designed for both single-phase and polyphase ac power systems, and selection
can be made with the
Phase mode
setting, which can be set either to the "Single Phase" or
"Three Phase" mode. The default setting is "Single Phase".
The basic difference between these alternatives depends on how many phases are needed
to have the voltage variation activated. When the
Phase mode
setting is "Single Phase",
the activation is straightforward. There is no dependence between the phases for variation
pickup. The
PICKUP
output and the corresponding phase pickup are activated when the
limit is exceeded or undershot. The corresponding phase pickup deactivation takes place
when the limit (includes small hysteresis) is undershot or exceeded. The
PICKUP
output
is deactivated when there are no more active phases.
1MRS240050-IB C
Section 8
Power quality measurement functions
REF615R
421
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...