Change of voltage dV/dt
•
Change of current dI/dt
The calculated delta quantities are compared to the respective set values of the
Current
change rate
and
Voltage change rate
settings.
The delta current and delta voltage algorithms detect a fuse failure if there is a sufficient
negative change in the voltage amplitude without a sufficient change in the current
amplitude in each phase separately. This is performed when the circuit breaker is closed.
Information about the circuit breaker position is connected to the
CB_CLOSED
input.
There are two conditions for activating the current and voltage delta function.
•
The magnitude of dV/dt exceeds the corresponding value of the
Voltage change rate
setting and magnitude of dI/dt is below the value of the
Current change rate
setting
in any phase at the same time due to the closure of the circuit breaker (
CB_CLOSED
= TRUE).
•
The magnitude of dV/dt exceeds the value of the
Voltage change rate
setting and the
magnitude of dI/dt is below the Current change rate setting in any phase at the same
time and the magnitude of the phase current in the same phase exceeds the
Min Op
current delta
setting.
The first condition requires the delta criterion to be fulfilled in any phase at the same time
as the circuit breaker is closed. Opening the circuit breaker at one end and energizing the
line from the other end onto a fault could lead to an improper operation of 60 with an open
breaker. If this is considered to be an important disadvantage, the
CB_CLOSED
input is to
be connected to FALSE. In this way only the second criterion can activate the delta
function.
The second condition requires the delta criterion to be fulfilled in one phase together with
a high current for the same phase. The measured phase current is used to reduce the risk
of a false fuse failure detection. If the current on the protected line is low, a voltage drop
in the system (not caused by the fuse failure) is not followed by a current change and a false
fuse failure can occur. To prevent this, the minimum phase current criterion is checked.
The fuse failure detection is active until the voltages return above the
Min Op voltage delta
setting. If a voltage in a phase is below the
Min Op voltage delta
setting, a new fuse failure
detection for that phase is not possible until the voltage returns above the setting value.
Decision logic
The fuse failure detection outputs
FUSEF_V
and
FUSEF_3PH
are controlled according
to the detection criteria or external signals.
1MRS240050-IB C
Section 6
Supervision functions
REF615R
373
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...