GUID-846395DB-B778-4782-A6FA-9D7B62D92F65-ANSI V2 EN
Figure 109:
Behavior of different IDMT reset modes. The value for Type of reset
curve is “Def time reset”. Also other reset modes are presented for the
time integrator.
The
Time multiplier
setting is used for scaling the IDMT trip times.
The
Minimum trip time
setting parameter defines the minimum desired trip time for
IDMT. The setting is applicable only when the IDMT curves are used.
The
Minimum trip time
setting should be used with care because the
operation time is according to the IDMT curve, but always at least the