mode
which selects the blocking mode. The
BLOCK
input can be controlled by a binary
input, a horizontal communication input or an internal signal of the protection relay's
program. The influence of the
BLOCK
signal activation is preselected with the global
setting
Blocking mode
.
The
Blocking mode
setting has three blocking methods. In the "Freeze timers" mode, the
operation timer is frozen to the prevailing value, but the
TRIP
output is not deactivated
when blocking is activated. In the "Block all" mode, the whole function is blocked and the
timers are reset. In the "Block TRIP output" mode, the function operates normally but the
TRIP
output is not activated.
4.1.4.5
Measurement modes
The function operates on three alternative measurement modes: "RMS", "DFT" and
"Peak-to-Peak". The measurement mode is selected with the
Measurement mode
setting.
Table 113:
Measurement modes supported by 51N/50N or 51G/50G stages
Measurement mode
51N/G
50N/G-1/2
50N/G-3
RMS
x
x
DFT
x
x
Peak-to-Peak
x
x
x
For a detailed description of the measurement modes, see the
4.1.4.6
Timer characteristics
51N/50N or 51G/50G supports both DT and IDMT characteristics. The user can select the
timer characteristics with the
Operating curve type
and
Type of reset curve
settings. When
the DT characteristic is selected, it is only affected by the
Trip delay time
and
Reset delay
time
settings.
The protection relay provides 16 IDMT characteristics curves, of which seven comply
with the IEEE C37.112 and six with the IEC 60255-3 standard. Two curves follow the
special characteristics of ABB praxis and are referred to as RI and RD. In addition to this,
a user programmable curve can be used if none of the standard curves are applicable. The
user can choose the DT characteristic by selecting the
Operating curve type
values "ANSI
Def. Time" or "IEC Def. Time". The functionality is identical in both cases.
The following characteristics, which comply with the list in the IEC 61850-7-4
specification, indicate the characteristics supported by different stages:
Section 4
1MRS240050-IB C
Protection functions
164
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...