of a blackout. 27 is also used to initiate voltage correction measures, such as insertion of
shunt capacitor banks, to compensate for a reactive load and thereby to increase the
voltage.
27 can be used to disconnect from the network devices, such as electric motors, which are
damaged when subjected to service under low voltage conditions. 27 deals with low
voltage conditions at power system frequency. Low voltage conditions can be caused by:
•
Malfunctioning of a voltage regulator or incorrect settings under manual control
(symmetrical voltage decrease)
•
Overload (symmetrical voltage decrease)
•
Short circuits, often as phase-to-ground faults (unsymmetrical voltage increase).
27 prevents sensitive equipment from running under conditions that could cause
overheating and thus shorten their life time expectancy. In many cases, 27 is a useful
function in circuits for local or remote automation processes in the power system.
4.2.2.7
Signals
Table 181:
27-1/2 Input signals
Name
Type
Default
Description
V_A_AB
SIGNAL
0
Phase to ground voltage A or phase to phase voltage AB
V_B_BC
SIGNAL
0
Phase to ground voltage B or phase to phase voltage BC
V_C_CA
SIGNAL
0
Phase to ground voltage C or phase to phase voltage
CA
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Table 182:
27-1/2 Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
1MRS240050-IB C
Section 4
Protection functions
REF615R
235
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...