SHIFT
HOLD
RESET
O6
O7
O8
O5
O4
O3
O2
O1
GUID-6A48BE57-4BDC-4E68-B8EF-6560DC6CA3E2 V1 EN
Figure 40:
Logic diagram with RESET input
3.13.1.5
Application
The shift selector function can be used in any application where it is desired to select
among exclusive modes of operation using a momentary push-button as user input. In the
example in
Figure
, the shifter outputs can be connected to the setting group inputs of the
protection function block. A push-button on the front panel can be configured as an input
to the shifter and multiple presses configure the protection relay to use the next setting
group.
RESET
SHFT
SHIFT
HOLD
O1
O2
O3
O4
O5
O6
O7
O8
To
Front Panel
LEDs
To
Front Panel
Push Buttons
GUID-17F364D7-9603-4056-BA9E-391C28C608CC V1 EN
Figure 41:
Using SHFT with a protection function to select a setting group
The
Ox enable
settings on SHFT must be used to disable outputs
O7
and
O8
since they are
not used. Specific setting groups can optionally be disabled also by setting the
corresponding output to “Disable”. Note that output
O1
requires no connection since the
protection function defaults to SG_1 when no inputs are TRUE.
The protection function must have the
SG operation mode
setting set to “Logic mode 1”.
The highest asserted input then determines the active setting group.
1MRS240050-IB C
Section 3
Basic functions
REF615R
93
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...