6.4
Cable fault detection CFD
6.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Cable fault detection
RCFD
RCFD
CFD
6.4.2
Function block
GUID-F730AEE9-271E-4CFD-893A-FFF525AF806F-ANSI V1 EN
Figure 199:
Function block
6.4.3
Functionality
The self-clearing cable fault detection function CFD calculates the half-cycle DFT of the
current signal for all three phases and uses it to detect a self-clearing fault pronounced
primarily in underground circuits.
The CFD function is reset 500 ms after detecting a cable fault to get ready for the next
fault. Fault counters are stored and can be cleared only manually.
The phase discontinuity protection function provides individual counter values for the
number of times a self-clearing fault is observed in each phase. The phase discontinuity
protection function also determines whether the self-clearing fault is observed in all three
phases or not.
This phase discontinuity protection contains a blocking functionality. It is possible to
block the function outputs or the function itself if desired.
6.4.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of CFD can be described with a module diagram. All the modules in the
diagram are explained in the next sections.
Section 6
1MRS240050-IB C
Supervision functions
378
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...