GUID-433F1AF8-DA0B-4FEA-A281-1872487F3B97 V1 EN
Figure 123:
Tripping curve of "OvExt IDMT Crv2" based on the settings specified in
example 3. The two dots marked on the curve are referred to in the text.
If the excitation level stays at 1.26, the tripping occurs after 26360 milliseconds as per the
marked dot in
. For the excitation level of 1.4, the second dot in
, the
curve "OvExt IDMT Crv2" gives 260 milliseconds as per
Minimum
trip time
setting limits the trip time to 1000 milliseconds. The
Maximum trip time
setting
limits the trip time to 1000000 milliseconds if the excitation level stays between 1.1 and
1.16.
In general, however, the excitation level seldom remains constant.
Therefore, the exact trip times in any inverse time mode are difficult to
predict.
Example 4
In this case, the function operation is according to IDMT. The
Operating curve type
setting is selected as "OvExt IDMT Crv4". The corresponding example settings for the
IDMT curve operation are given as:
Pickup value
= 110%,
Voltage Max Cont
= 100%,
1MRS240050-IB C
Section 4
Protection functions
REF615R
259
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...