Figure 89:
Operating characteristic I
0
sin(φ) in forward fault
The operating sector is limited by angle correction, that is, the operating sector is 180
degrees - 2*(angle correction).
Example 2.
Iosin(φ) criterion selected, reverse-type fault
=> FAULT_DIR = 2
1MRS240050-IB C
Section 4
Protection functions
REF615R
189
Technical Manual