192 . 168 .
10
.
187
L D P 1
0 A
B B
L D P 1 . C F G
0 A
B B
L D P 1 . D A T
GUID-43078009-323D-409C-B84A-5EB914CDEE53 V1 EN
Figure 52:
Load profile record file naming
3.15.1.4
Clearing of record
The load profile record can be cleared with
Reset load profile rec
via HMI,
communication or the ACT input in PCM600. Clearing of the record is allowed only on
the engineer and administrator authorization levels.
The load profile record is automatically cleared if the quantity selection parameters are
changed or any other parameter which affects the content of the COMTRADE
configuration file is changed. Also, if data source for selected quantity is removed, for
example, with ACT, the load profile recorder stops recording and previously collected
data are cleared.
3.15.2
Configuration
The load profile record can be configured with the PCM600 tool or any tool supporting the
IEC 61850 standard.
The load profile record can be enabled or disabled with the
Operation
setting under the
Configuration/Load Profile Record
menu.
The recording buffer is filled in FIFO manner, meaning that oldest data is overwritten by
newest data. If oldest data is considered important,
Mem. warning level
and
Mem. alarm
1MRS240050-IB C
Section 3
Basic functions
REF615R
107
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...