A070552-ANSI V1 EN
Figure 61:
Functional module diagram. I_A, I_B and I_C represent phase currents.
Level detector
The measured phase currents are compared phasewise to the set
Pickup value
. If the
measured value exceeds the set
Pickup value
, the level detector reports the exceeding of
the value to the phase selection logic. If the
ENA_MULT
input is active, the
Pickup value
setting is multiplied by the
Pickup value Mult
setting.
The pickup value multiplication is normally done when the inrush detection function
(INR) is connected to the
ENA_MULT
input.
GUID-640654EC-1E77-4ED5-BE41-9EC399B686BA-ANSI V1 EN
Figure 62:
Pickup value behavior with
ENA_MULT
input activated
Section 4
1MRS240050-IB C
Protection functions
132
REF615R
Technical Manual