Name
Type
Default
Description
V_A_AB
SIGNAL
0
Phase-to-ground voltage A or phase-to-phase voltage
AB
V_B_BC
SIGNAL
0
Phase-to-ground voltage B or phase-to-phase voltage
BC
V_C_CA
SIGNAL
0
Phase-to-ground voltage C or phase-to-phase voltage
CA
V
1
SIGNAL
0
Positive-phase sequence voltage
F
SIGNAL
0
Measured frequency
BLOCK
BOOLEAN
0=False
Block signal
Table 202:
24 Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
BLK_RESTART
BOOLEAN
Signal for blocking reconnection of an overheated
machine
COOL_ACTIVE
BOOLEAN
Signal to indicate machine is in cooling process
4.2.5.8
Settings
Table 203:
24 Group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
100...200
%
1
100
Over excitation pickup value
Operating curve type
5=ANSI DT
15=IEC DT
17=OvExt IDMT
Crv1
18=OvExt IDMT
Crv2
19=OvExt IDMT
Crv3
20=OvExt IDMT
Crv4
15=IEC DT
Selection of time delay curve type
Time multiplier
0.1...100.0
0.1
3.0
Time multiplier for Overexcitation IDMT curves
Trip delay time
200...200000
ms
10
500
Trip delay time in definite- time mode
1MRS240050-IB C
Section 4
Protection functions
REF615R
261
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...