Table 453:
EIA-232 and EIA-485 jumper connectors for COM1
Group
Jumper connection
Description
X19
1–2
2–3
EIA-485
EIA-232
X20
1–2
2–3
EIA-485
EIA-232
X21
1–2
2–3
EIA-485
EIA-232
X26
1–2
2–3
EIA-485
EIA-232
To ensure fail-safe operation, the bus is to be biased at one end using the pull-up and pull-
down resistors on the communication module. In the 4-wire connection, the pull-up and
pull-down resistors are selected by setting jumpers X5, X6, X8, X9 to the enabled
position. The bus termination is selected by setting jumpers X7, X11 to the enabled
position.
The jumpers have been set to no termination and no biasing as default.
Table 454:
2-wire EIA-485 jumper connectors for COM1
Group
Jumper connection
Description
Notes
X5
1–2
2–3
A+ bias enabled
A+ bias disabled
1)
COM1
Rear connector X6
2-wire connection
X6
1–2
2–3
B- bias enabled
B- bias disabled
X7
1–2
Bus termination enabled
2–3
Bus termination disabled
1) Default setting
Table 455:
4–wire EIA-485 jumper connectors for COM1
Group
Jumper connection
Description
Notes
X5
1–2
2–3
A+ bias enabled
A+ bias disabled
1)
COM1
Rear connector X6
4-wire TX channel
X6
1–2
2–3
B- bias enabled
B- bias disabled
X7
1–2
Bus termination enabled
2–3
Bus termination disabled
Table continues on next page
Section 14
1MRS240050-IB C
Protection relay's physical connections
636
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...