When applied to replace DPU2000R, the two instances of 86/94 can be applied to mimic
the DPU2000R master trip feature. The programmability using graphic interfaces in the
protection relay allows programming of more functions than allowed in DPU2000R.
GUID-FDEAFAB7-E3DB-44F8-B383-A9512D610D27 V1 EN
Figure 163:
Typical 86/94 connection
5.3.6
Signals
Table 260:
86/94 Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0=False
Block of function
TRIP
BOOLEAN
0=False
Trip
RST_LKOUT
BOOLEAN
0=False
Input for resetting the circuit breaker lockout function
Table 261:
86/94 Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip output signal
CL_LKOUT
BOOLEAN
Circuit breaker lockout output (set until reset)
1MRS240050-IB C
Section 5
Protection-related functions
REF615R
331
Technical Manual