When the reclosing is initiated with pickup of the protection function, the autoreclosing
function can execute the final trip of the circuit breaker in a short trip time, provided that
the fault still persists when the last selected reclosing has been carried out.
9.2.3.1
Protection signal definition
The
Control line
setting defines which of the initiation signals are protection pickup and
trip signals and which are not. With this setting, the user can distinguish the blocking
signals from the protection signals. The
Control line
setting is a bit mask, that is, the lowest
bit controls the
INIT_1
line and the highest bit the
INIT_6
line. Some example
combinations of the
Control line
setting are as follows:
Table 367:
Control line setting definition
Control line
setting
INIT_1
INIT_2
DEL_INIT_2
INIT_3
DEL_INIT_3
INIT_4
DEL_INIT_4
INIT_5
INIT_6
0
other
other
other
other
other
other
1
prot
other
other
other
other
other
2
other
prot
other
other
other
other
3
prot
prot
other
other
other
other
4
other
other
prot
other
other
other
5
prot
other
prot
other
other
other
...63
prot
prot
prot
prot
prot
prot
prot =
protection signal
other =
non-protection signal
When the corresponding bit or bits in both the
Control line
setting and the
INIT_X
line
are TRUE:
•
The
CLOSE_CB
output is blocked until the protection is reset
•
If the
INIT_X
line defined as the protection signal is activated during the
discrimination time, the AR function goes to lockout
•
If the
INIT_X
line defined as the protection signal stays active longer than the time
set by the
Max trip time
setting, the AR function goes to lockout (long trip)
•
The
UNSUC_RECL
output is activated after a pre-defined two minutes (alarming
ground-fault).
Section 9
1MRS240050-IB C
Control functions
458
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...