immediately when the current exceeds the set
Pickup value
and the
PICKUP
output is
activated.
The
TRIP
output of the component is activated when the cumulative sum of the integrator
calculating the overcurrent situation exceeds the value set by the inverse-time mode. The
set value depends on the selected curve type and the setting values used. The curve scaling
is determined with the
Time multiplier
setting.
There are two methods to level out the inverse-time characteristic.
•
The
Minimum trip time
setting defines the minimum operating time for the IDMT
curve, that is, the operation time is always at least the
Minimum trip time
setting.
•
Alternatively, the
IDMT Sat point
is used for giving the leveling-out point as a
multiple of the
Pickup value
setting. (Global setting:
Configuration/System/IDMT
Sat point
). The default parameter value is 50. This setting affects only the overcurrent
and ground-fault IDMT timers.
IDMT operation time at currents over 50 x In is not guaranteed.
1MRS240050-IB C
Section 12
General function block features
REF615R
571
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...