The operation of CCM can be described with a module diagram. All the modules in the
diagram are explained in the next sections.
GUID-A4F2DBEE-938F-4961-9DAD-977151DDBA13 V1 EN
Figure 190:
Functional module diagram
Differential current monitoring
Differential current monitoring supervises the difference between the summed phase
currents I_A, I_B and I_C and the reference current I_REF.
The current operating characteristics can be selected with the
Pickup value
setting. When
the highest phase current is less than 1.0 × In, the differential current limit is defined with
Pickup value
. When the highest phase current is more than 1.0 × In, the differential current
limit is calculated with the equation.
MAX I
A I
B I C
Pickup value
( _ , _ , _
)
×
GUID-41E8DD52-0C7D-406D-9799-DA48A660D8E5-ANSI V1 EN
(Equation 20)
The differential current is limited to 1.0 × In.