3.13.3
Local/remote control function block CONTROL
3.13.3.1
Function block
GUID-15CBBF2C-3480-449D-A145-33D57A35B5F5 V1 EN
Figure 51:
Function block
3.13.3.2
Functionality
Local/Remote control is by default realized through the R/L button on the front panel. The
control via binary input can be enabled by setting the value of the
LR control
setting to
"Binary input".
The actual Local/Remote control state is evaluated by the priority scheme on the function
block inputs. If more than one input is active, the input with the highest priority is selected.
The actual state is reflected on the CONTROL function outputs. Only one output is active
at a time.
Table 57:
Truth table for CONTROL
Input
Output
CTRL_OFF
CTRL_LOC
CTRL_STA
1)
CTRL_REM
TRUE
any
any
any
OFF = TRUE
FALSE
TRUE
any
any
LOCAL = TRUE
FALSE
FALSE
TRUE
any
STATION = TRUE
FALSE
FALSE
FALSE
TRUE
REMOTE = TRUE
FALSE
FALSE
FALSE
FALSE
OFF = TRUE
1) If station authority is not in use, the
CTRL_STA
input is interpreted as
CTRL_REM
.
The station authority check based on the IEC 61850 command originator category in
control command can be enabled by setting the value of the
Station authority
setting to
"Station, Remote" (The command originator validation is performed only if the
LR
control
setting is set to "Binary input"). The station authority check is not in use by default.
1MRS240050-IB C
Section 3
Basic functions
REF615R
101
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...