Table 143:
67/50N Input signals
Name
Type
Default
Description
I0 or IG or I2
SIGNAL
0
Zero Sequence current / Negative sequence current
V0 or VG or V2
SIGNAL
0
Zero Sequence voltage / Negative sequence voltage
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
ENA_MULT
BOOLEAN
0=False
Enable signal for current multiplier
RCA_CTL
BOOLEAN
0=False
Relay characteristic angle control
Table 144:
67/51N Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
Table 145:
67/50N Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
4.1.5.11
Settings
Table 146:
67/51N Group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
0.010...5.000
xIn
0.005
0.010
Pickup value
Pickup value mult
0.8...10.0
0.1
1.0
Multiplier for scaling the pickup value
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Time multiplier
0.05...15.00
0.01
1.00
Time multiplier in IEC/ANSI IDMT curves
Table continues on next page
1MRS240050-IB C
Section 4
Protection functions
REF615R
199
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...