in a power system indicates that the generated power is too low to meet the demands of the
load connected to the power grid.
The underfrequency can occur as a result of the overload of generators operating in an
isolated system. It can also occur as a result of a serious fault in the power system due to
the deficit of generation when compared to the load. This can happen due to a fault in the
grid system on the transmission lines that link two parts of the system. As a result, the
system splits into two with one part having the excess load and the other part the
corresponding deficit.
The frequency gradient is applicable in all the situations where the change of the
fundamental power system voltage frequency should be detected reliably. The frequency
gradient can be used for both increasing and decreasing the frequencies. This function
provides an output signal suitable for load shedding, generator shedding, generator
boosting, set point change in sub-transmission DC systems and gas turbine startup. The
frequency gradient is often used in combination with a low frequency signal, especially in
smaller power systems where the loss of a large generator requires quick remedial actions
to secure the power system integrity. In such situations, the load shedding actions are
required at a rather high frequency level. However, in combination with a large negative
frequency gradient, the underfrequency protection can be used at a high setting.
4.3.1.6
Signals
Table 209:
81 Input signals
Name
Type
Default
Description
F
SIGNAL
0
Measured frequency
dF/dt
SIGNAL
0
Rate of change of frequency
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Table 210:
81 Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
OPR_OFRQ
BOOLEAN
Trip signal for overfrequency
OPR_UFRQ
BOOLEAN
Trip signal for underfrequency
OPR_FRG
BOOLEAN
Trip signal for frequency gradient
PICKUP
BOOLEAN
Pickup
ST_OFRQ
BOOLEAN
Pickup signal for overfrequency
ST_UFRQ
BOOLEAN
Pickup signal for underfrequency
ST_FRG
BOOLEAN
Pickup signal for frequency gradient
1MRS240050-IB C
Section 4
Protection functions
REF615R
269
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...