Table 397:
FLO Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Line length
0.0...300.0
0.1
100.0
Length of the Line in miles or Km
R1
0.000...20.000
ohm
0.001
1.000
Pos Seq Resistance in ohms/(miles or Km)
X1
0.000...30.000
ohm
0.001
2.000
Pos seq reactance in ohms/(miles or Km)
R0
0.000...20.000
ohm
0.001
0.010
Pos Seq Resistance in ohms/(miles or Km)
X0
0.000...30.000
ohm
0.001
1.000
Zero Seq Reactance in ohms/(miles or Km)
10.2.7
Monitored data
Table 398:
FLO Monitored data
Name
Type
Values (Range)
Unit
Description
FLT_DIST
FLOAT32
0.00...9999.00
Fault Distance
FLT_LOOP
Enum
1=AG Fault
2=BG Fault
3=CG Fault
4=AB Fault
5=BC Fault
6=CA Fault
7=ABC Fault
-1=ABG Fault
-2=BCG Fault
-3=CAG Fault
-4=ABCG Fault
0=No fault
Fault Loop
FLT_R
FLOAT32
0.00...999.00
ohm
FaultResistance
XF_LOOP
FLOAT32
0.00...9999.00
ohm
Loop Reactance
TIME_FLT_LOC
Timestamp
Time stamp
FLO
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Section 10
1MRS240050-IB C
Recording functions
532
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...