4.1.5.13
Technical data
Table 152:
67/51N and 67/50N Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
67/51N
Current:
±1.5% of the set value or ±0.002 × I
n
Voltage
±1.5% of the set value or ±0.002 × V
n
Phase angle:
±2°
67/50N-1 and 67/50N-2
Current:
±1.5% of the set value or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0% of the set value
(at currents in the range of 10…40 × I
n
)
Voltage:
±1.5% of the set value or ±0.002 × V
n
Phase angle:
±2°
Pickup time
1)2)
Minimum
Typical
Maximum
67/50N-2 and 67/51N
and 67/50N-1:
I
Fault
= 2 × set
Pickup
value
62 ms
65 ms
69 ms
Reset time
<40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Trip time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Trip time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
1)
Measurement mode = default (depends on stage), current before fault = 0.0 × I
n
, f
n
= 60 Hz, ground-fault
current with nominal frequency injected from random phase angle, results based on statistical distribution of
1000 measurements
2) Includes the delay of the signal output contact
3) Maximum
Pickup value = 2.5 × I
n
,
Pickup value multiples in range of 1.5...20
Section 4
1MRS240050-IB C
Protection functions
204
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...