An example of a delayed reset in the inverse time characteristics. When
the pickup becomes active during the reset period, the trip time counter
continues from the level corresponding to the drop-off (reset time = 0.50 ·
Cooling time)
Overexcitation IDMT curves 1, 2 and 3
The base equation for the IDMT curves "OvExt IDMT Crv1", "OvExt IDMT Crv2" and
"OvExt IDMT Crv3" is:
t s
e
ak
b
M
c
( )
=
⋅
+ −
60
100
GUID-5D74EA35-03AD-44D1-9EE0-0B1999C55BF1 V1 EN
(Equation 5)
t(s) Trip time in seconds
M
Excitation level (V/f ratio or volts/hertz) in pu
k
Time multiplier setting
The constant "60" in
converts time from minutes to seconds.
Section 4
1MRS240050-IB C
Protection functions
252
REF615R
Technical Manual