1.
SendDataUDP[x]
– Enable / disable UDP data stream
2.
ProtocolOnUDP[x]
– Send IEEE1344 or C37.118 on UDP
3.
PMUReportUDP[x]
– Instance number of PMUREPORT function block that must
send data on this UDP stream (UDP client group[x])
4.
UDPDestAddres[x]
– UDP destination address for UDP client group[x] (unicast /
multicast address range)
5.
UDPDestPort[x]
– UDP destination port number for UDP client group[x]
6.
TCPportUDPdataCtrl[x]
– TCP port to control of data sent over UDP client
group[x], i.e. to receive commands and send configuration frames
7.
MCastCtrlPortSel[x]
– Physical network port selection to route multicast data
8.
SendCfgOnUDP[x]
– Send configuration frame 2 (CFG-2) on UDP for client
group[x]
It is possible to turn off/on the UDP data communication either by setting the parameter
SendDataUDP[x]
to
Disable/Enable
locally in the PMU or by sending a C37.118 or
IEEE1344 command frame (
RTDOFF/RTDON
) remotely from the client to the PMU as
defined in IEEE 1344/C37.118 standard.
However, such a remote control to stop the streams from the client is only possible when
the parameter
SendDataUDP[x]
is set to
SetByProtocol
. The command
RTDOFF/
RTDON
sent by the client is stored in the IED, i.e. if the RES670 is rebooted for some
reason, the state of the stream will remain the same.
If the parameter
SendDataUDP[x]
is set
Enable
the
RTDOFF/RTDON
commands
received from the clients are ignored in RES670.
It is recommended not to set the parameter
SendDataUDP[x]
to
SetByProtocol
in case of
a multicast. This is because if one of the clients sends the
RTDOFF
command, all the
clients will stop receiving the frames.
The UDP implementation in RES670 is a UDP_TCP. This means that by default, only the
data frames are sent out on UDP stream and the header frame, configuration frame and
command frame are sent over TCP. This makes the communication more reliable
especially since commands are sent over TCP which performs request/acknowledgment
exchange to ensure that no data (command in this case) is lost.
However, by setting the parameter
SendCfgOnUDP[x]
to
Enable
, the configuration frame
2 (CFG-2) of IEEEC37.118 data stream is cyclically sent on the corresponding UDP
stream (UDP client group[x]) once per minute. This is useful in case of multicast UDP data
stream when a lot of PMU clients are receiving the same UDP stream from the same UDP
group (UDP client group[x]).
As shown in Figure
, there are maximum 2 instances of PMUREPORT function blocks
available in RES670. Each UDP client group[x] can only connect to one of the
PMUREPORT instances at the same time. This is defined in the PMU by the parameter
1MRK 511 365-UUS A
Section 6
Wide area measurement system
Phasor measurement unit RES670 2.1 ANSI
105
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...