Table 629:
DOSLANCD Output signals
Name
Type
Description
LINKUP
BOOLEAN
Ethernet link status
WARNING
BOOLEAN
Frame rate is higher than normal state
ALARM
BOOLEAN
Frame rate is higher than throttle state
20.19.4
Settings
The function does not have any parameters available in the local HMI or PCM600.
20.19.5
Monitored data
Table 630:
DOSFRNT Monitored data
Name
Type
Values (Range)
Unit
Description
State
INTEGER
0=Off
1=Normal
2=Throttle
3=DiscardLow
4=DiscardAll
5=StopPoll
-
Frame rate control state
Quota
INTEGER
-
%
Quota level in percent 0-100
Table 631:
DOSLANAB Monitored data
Name
Type
Values (Range)
Unit
Description
DoSStatus
INTEGER
0=Off
1=Normal
2=Throttle
3=DiscardLow
4=DiscardAll
5=StopPoll
-
Frame rate control state
Quota
INTEGER
-
%
Quota level in percent 0-100
Table 632:
DOSLANCD Monitored data
Name
Type
Values (Range)
Unit
Description
DoSStatus
INTEGER
0=Off
1=Normal
2=Throttle
3=DiscardLow
4=DiscardAll
5=StopPoll
-
Frame rate control state
Quota
INTEGER
-
%
Quota level in percent 0-100
Section 20
1MRK 511 365-UUS A
Basic IED functions
748
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...