of rated current. The compensation below 5% and above 100% is constant and linear in
between, see figure
Phase currents (magnitude and angle) are available on the outputs and each magnitude
output has a corresponding supervision level output (Ix_RANGE). The supervision
output signal is an integer in the interval 0-4, see section
.
16.1.7.4
Phase-phase and phase-neutral voltage measurements VMMXU,
VNMMXU
The voltage function must be connected to three-phase voltage input in the configuration
tool to be operable. Voltages are handled in the same way as currents when it comes to
class 0.5 calibrations, see above.
The voltages (phase or phase-phase voltage, magnitude and angle) are available on the
outputs and each magnitude output has a corresponding supervision level output
(Vxy_RANG). The supervision output signal is an integer in the interval 0-4, see section
16.1.7.5
Voltage and current sequence measurements VMSQI, CMSQI
The measurement functions must be connected to three-phase current (CMSQI) or voltage
(VMSQI) input in the configuration tool to be operable. No outputs, other than X_RANG,
are calculated within the measuring blocks and it is not possible to calibrate the signals.
Input signals are obtained from the pre-processing block and transferred to corresponding
output.
Positive, negative and three times zero sequence quantities are available on the outputs
(voltage and current, magnitude and angle). Each magnitude output has a corresponding
supervision level output (X_RANGE). The output signal is an integer in the interval 0-4,
see section
16.1.8
Technical data
Table 407:
CVMMXN technical data
Function
Range or value
Accuracy
Frequency
(0.95-1.05) x f
n
±
2.0 mHz
Voltage
(10 to 300) V
±
0.3% of V at V
≤
50 V
±
0.2% of V at V
>
50 V
Current
(0.1-4.0) x I
n
±
0.8% of I at 0.1 x I
n
<
I
<
0.2 x I
n
±
0.5% of I at 0.2 x I
n
<
I
<
0.5 x I
n
±
0.2% of I at 0.5 x I
n
<
I
<
4.0 x I
n
Table continues on next page
Section 16
1MRK 511 365-UUS A
Monitoring
516
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...