Section 13
Secondary system supervision
13.1
Current circuit supervision (87)
13.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current circuit supervision
CCSSPVC
-
87
13.1.2
Functionality
Open or short circuited current transformer cores can cause unwanted operation of many
protection functions such as differential, ground-fault current and negative-sequence
current functions.
Current circuit supervision (CCSSPVC, 87) compares the residual current from a three
phase set of current transformer cores with the neutral point current on a separate input
taken from another set of cores on the current transformer.
A detection of a difference indicates a fault in the circuit and is used as alarm or to block
protection functions expected to give inadvertent tripping.
13.1.3
Function block
CCSSPVC (87)
I3P*
IREF*
BLOCK
FAIL
ALARM
ANSI13000304-1-en.vsd
ANSI13000304 V1 EN
Figure 123:
CCSSPVC (87) function block
Signal IREF must be connected in the configuration.
1MRK 511 365-UUS A
Section 13
Secondary system supervision
Phasor measurement unit RES670 2.1 ANSI
359
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...