15.12.7
Technical data
Table 358:
Number of IB16 instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
IB16
6
4
8
15.13
Integer to Boolean 16 conversion with logic node
representation ITBGAPC
15.13.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Integer to boolean 16 conversion with
logic node representation
ITBGAPC
-
-
15.13.2
Functionality
Integer to boolean conversion with logic node representation function ITBGAPC is used
to transform an integer which is transmitted over IEC 61850 and received by the function
to 16 binary coded (logic) output signals.
ITBGAPC function can only receive remote values over IEC 61850 when the R/L
(Remote/Local) push button on the front HMI, indicates that the control mode for the
operator is in position R (Remote i.e. the LED adjacent to R is lit ), and the corresponding
signal is connected to the input PSTO ITBGAPC function block. The input BLOCK will
freeze the output at the last received value and blocks new integer values to be received
and converted to binary coded outputs.
Section 15
1MRK 511 365-UUS A
Logic
468
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...