9.2.8
Technical data
Table 162:
OV2PTOV (59) technical data
Function
Range or value
Accuracy
Trip voltage, step 1
and 2
(1.0-200.0)% of
VBase
±0.5% of V
n
at V ≤ V
n
±0.5% of V at V > V
n
Absolute hysteresis
(0.0–50.0)% of
VBase
±0.5% of V
n
at V ≤ V
n
±0.5% of V at V > V
n
Inverse time
characteristics for
steps 1 and 2, see
-
Definite time delay,
low step (step 1) at 0
to 1.2 x V
set
(0.00 - 6000.00) s
±0.2% or ±45 ms whichever is
greater
Definite time delay,
high step (step 2) at 0
to 1.2 x V
set
(0.000-60.000) s
±0.2% or ±45 ms whichever is
greater
Minimum trip time,
Inverse
characteristics
(0.000-60.000) s
±0.2% or ±45 ms whichever is greater
Trip time, pickup at 0
to 2 x V
set
Min. = 15 ms
Max. = 30 ms
-
Reset time, pickup at
2 to 0 x V
set
Min. = 15 ms
Max. = 30 ms
-
Trip time, pickup at 0
to 1.2 x V
set
Min. = 20 ms
Max. = 35 ms
-
Reset time, , pickup
at 1.2 to 0 x V
set
Min. = 5 ms
Max. = 25 ms
-
Critical impulse time
10 ms typically at 0 to 2 x V
set
-
Impulse margin time
15 ms typically
-
Section 9
1MRK 511 365-UUS A
Voltage protection
296
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...