Trip from this function can be blocked from the binary input BLKTRDIR.
When the function picks up, binary output signals PICKUP and PUDIRIN are activated.
If the output signals PICKUP and PUDIRIN remain active for the set delay
tDef
the binary
output signals TRIP and TRDIRIN get activated.
The function indicates forward/reverse direction to the fault. Reverse direction is defined
as φ is within the angle sector:
RCADir
+ 180° ±
ROADir
This variant has definite time delay.
Directional functions
For all the directional functions there are directional pickup signals PUFW: fault in the
forward direction, and PUREV: fault in the reverse direction. Even if the directional
function is set to operate for faults in the forward direction, a fault in the reverse direction
will give the pickup signal PUREV. Also if the directional function is set to operate for
faults in the reverse direction, a fault in the forward direction will give the pickup signal
PUFW.
Non-directional ground fault current protection
This function will measure the residual current without checking the phase angle. The
function will be used to detect cross-country faults. This function can serve as alternative
or backup to distance protection with phase preference logic. To assure selectivity the
distance protection can block the non-directional ground fault current function via the
input BLKNDN.
The non-directional function is using the calculated residual current, derived as sum of the
phase currents. This will give a better ability to detect cross-country faults with high
residual current, also when dedicated core balance CT for the sensitive ground fault
protection will saturate.
This variant has the possibility of choice between definite time delay and inverse time
delay (
TimeChar
parameter). The inverse time delay shall be according to IEC 60255-3.
For trip, the residual current 3I
0
shall be larger than the set level (
INNonDirPU
).
Trip from this function can be blocked from the binary input BLKNDN.
When the function picks up, binary output signal PUNDIN is activated. If the output signal
PUNDIN remains active for the set delay
tINNonDir
or after the inverse time delay the
binary output signals TRIP and TRNDIN get activated.
Residual overvoltage release and protection
All the directional functions shall be released when the residual voltage gets higher than
a set level
VNRelPU
.
Section 8
1MRK 511 365-UUS A
Current protection
238
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...