unconditionally on the input
IN
value
•
reset the value of the nonvolatile memory to zero
•
BLOCK
: Freeze the integration and block/reset the other outputs
•
unconditionally on the signal value
•
BLOCK
request overrides
RESET
request
•
Monitor and report the conditions of limit transgression
•
overflow if output
ACCTIME
>999999.9 seconds
•
alarm if
ACCTIME
>
tAlarm
•
warning if
ACCTIME
>
tWarning
The
ACCTIME
output represents the integrated time in seconds while
tOverflow
,
tAlarm
and
tWarning
are the time limit parameters in seconds.
tAlarm
and
tWarning
are user settable limits. They are also independent, that is, there is
no check if
tAlarm
>
tWarning
.
tAlarm
and
tWarning
are possible to be defined with a resolution of 10 ms, depending on
the level of the defined values for the parameters.
The limit for the overflow supervision is fixed at 999999.9 seconds. The outputs freeze if
an overflow occurs.
15.14.6.1
Operation accuracy
The accuracy of TEIGAPC depends on essentially three factors
•
function cycle time
•
the pulse length
•
the number of pulses, that is, the number of rising and falling flank pairs
In principle, a shorter function cycle time, longer integrated time length or more pulses
may lead to reduced accuracy.
15.14.6.2
Memory storage
The value of the integrated elapsed time is retained in a non-volatile memory.
1MRK 511 365-UUS A
Section 15
Logic
Phasor measurement unit RES670 2.1 ANSI
475
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...