15.7.2.3
Technical data
Table 311:
Number of INDCOMBSPQT instances
Logic block
Quantity with cycle time
3 ms
8 ms
100 ms
INDCOMBSPQT
-
10
10
15.7.3
Single point input signal attributes converting function block
INDEXTSPQT
The value part of the single point input signal SI_IN is copied to SI_OUT output. The time
part of single point input is copied to the TIME output. The state bits in the common part
and the indication part of the input signal are copied to the corresponding state output.
INDEXTSPQT can propagate the quality, the value and the time stamps of the signals via
IEC61850.
15.7.3.1
Function block
INDEXTSPQT
SI_IN*
SI_OUT
TIME
BLOCKED
SUBST
INVALID
TEST
IEC14000067-1-en.vsd
IEC14000067 V1 EN
Figure 161:
INDEXTSPQT function block
15.7.3.2
Signals
Table 312:
INDEXTSPQT Input signals
Name
Type
Default
Description
SI_IN
BOOLEAN
0
Single indication
Section 15
1MRK 511 365-UUS A
Logic
444
Phasor measurement unit RES670 2.1 ANSI
Technical manual