Function
Range or value
Accuracy
Reset time, pickup at f
set
+0.02 Hz
to f
set
-0.02 Hz
Min. = 15 ms
Max. = 30 ms
-
Trip time, definite time function at
f
set
-0.02 Hz to f
set
+0.02 Hz
(0.000-60.000)s
±0.2% ±100 ms
whichever is greater
Reset time, definite time function
at f
set
+0.02 Hz to f
set
-0.02 Hz
(0.000-60.000)s
±0.2% ±120 ms,
whichever is greater
10.3
Rate-of-change frequency protection SAPFRC (81)
10.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Rate-of-change frequency protection
SAPFRC
df/dt
><
SYMBOL-N V1 EN
81
10.3.2
Functionality
The rate-of-change frequency protection function SAPFRC (81) gives an early indication
of a main disturbance in the system. SAPFRC (81) measures frequency with high
accuracy, and can be used for generation shedding, load shedding and remedial action
schemes. SAPFRC (81) can discriminate between a positive or negative change of
frequency. A definite time delay is provided for trip.
SAPFRC (81) is provided with an undervoltage blocking. The operation is based on
positive sequence voltage measurement and requires two phase-phase or three phase-
neutral voltages to be connected. For information about how to connect analog inputs,
refer to
Application manual/IED application/Analog inputs/Setting guidelines
.
Section 10
1MRK 511 365-UUS A
Frequency protection
308
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...