6.2
Protocol reporting via IEEE 1344 and C37.118
PMUREPORT
6.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Protocol reporting via IEEE 1344 and
C37.118
PMUREPORT
-
-
6.2.2
Functionality
The phasor measurement reporting block moves the phasor calculations into an IEEE
C37.118 and/or IEEE 1344 synchrophasor frame format. The PMUREPORT block
contains parameters for PMU performance class and reporting rate, the IDCODE and
Global PMU ID, format of the data streamed through the protocol, the type of reported
synchrophasors, as well as settings for reporting analog and digital signals.
The message generated by the PMUREPORT function block is set in accordance with the
IEEE C37.118 and/or IEEE 1344 standards.
There are settings for Phasor type (positive sequence, negative sequence or zero sequence
in case of 3-phase phasor and A, B or C in case of single phase phasor), PMU's Service
class (Protection or Measurement), Phasor representation (polar or rectangular) and the
data types for phasor data, analog data and frequency data.
Synchrophasor data can be reported to up to 8 clients over TCP and/or 6 UDP group clients
for multicast or unicast transmission of phasor data from RES670. More information
regarding synchrophasor communication structure and TCP/UDP configuration is
available in section
C37.118 Phasor Measurement Data Streaming Protocol
Multiple PMU functionality can be configured in RES670, which can stream out same or
different data at different reporting rates or different performance (service) classes. There
are 2 instances of PMU functionality available in RES670. Each instance of PMU
functionality includes a set of PMU reporting function blocks tagged by the same instance
number (1 or 2). As shown in the following figures, each set of PMU reporting function
blocks includes PMUREPORT, PHASORREPORT1-4, ANALOGREPORT1-3, and
BINARYREPORT1-3 function blocks. In general, each instance of PMU functionality
has 32 configurable phasor channels (PHASORREPORT1–4 blocks), 24 analog channels
(ANALOGREPORT1-3 blocks), and 28 digital channels (24 digital-report channels in
BINARYREPORT1-3 and 4 trigger-report channels in PMUREPORT function block).
Special rules shall be taken into account in PCM600 for Application Configuration and
Section 6
1MRK 511 365-UUS A
Wide area measurement system
110
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...