8.5.8
Technical data
Table 132:
LFPTTR/LCPTTR (26)technical data
Function
Range or value
Accuracy
Reference current
(2-400)% of IBase
±1.0% of I
n
Reference temperature
(0-600)°F, 0 - 300)°C
±
2.0°F, ±2.0°C
Trip time:
2
2
2
2
2
ln
p
Trip
Amb
p
ref
ref
I
I
t
T
T
I
I
I
T
t
-
=
-
-
-
×
é
ù
ê
ú
ê
ú
ê
ú
ê
ú
ë
û
EQUATION13000039 V2 EN
(Equation 27)
T
Trip
= set trip temperature
T
Amb
= ambient temperature
T
ref
= temperature rise above ambient at I
ref
I
ref
= reference load current
I = actual measured current
I
p
= load current before overload occurs
Time constant
t
= (1–1000)
minutes
IEC 60255-149, ±5.0%
or ±200 ms whichever
is greater
Alarm temperature
(0-400)°F, (0-200)°C
±4.0°F, ±2.0°C
Trip temperature
(0-300)°C, (0-600)°F
±4.0°F, ±2.0°C
Reset level temperature
(0-300)°C, (0-600)°F
±4.0°F, ±2.0°C
8.6
Directional underpower protection GUPPDUP (37)
8.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional underpower protection
GUPPDUP
P <
2
SYMBOL-LL V2 EN
37
8.6.2
Functionality
The task of a generator in a power plant is to convert mechanical energy available as a
torque on a rotating shaft to electric energy.
1MRK 511 365-UUS A
Section 8
Current protection
Phasor measurement unit RES670 2.1 ANSI
249
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...