Name
Values (Range)
Unit
Step
Default
Description
tReset4
0.000 - 60.000
s
0.001
0.020
Reset time delay for step 4
tPCrv4
0.005 - 3.000
-
0.001
1.000
Param P for customized inverse trip time curve
for step 4
tACrv4
0.005 - 200.000
-
0.001
13.500
Param A for customized inverse trip time curve
for step 4
tBCrv4
0.00 - 20.00
-
0.01
0.00
Param B for customized inverse trip time curve
for step 4
tCCrv4
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse trip time curve
for step 4
tPRCrv4
0.005 - 3.000
-
0.001
0.500
Param PR for customized inverse reset time
curve for step 4
tTRCrv4
0.005 - 100.000
-
0.001
13.500
Param TR for customized inverse reset time
curve for step 4
tCRCrv4
0.1 - 10.0
-
0.1
1.0
Param CR for customized inverse reset time
curve for step 4
Table 103:
EF4PTOC (51N_67N) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
SeqTypeIDir
Zero seq
Neg seq
-
-
Zero seq
Choice of measurand for directional current
SeqTypeIPol
Zero seq
Neg seq
-
-
Zero seq
Choice of measurand for polarizing current
SeqTypeVPol
Zero seq
Neg seq
-
-
Zero seq
Choice of measurand for polarizing voltage
Table 104:
EF4PTOC (51N_67N) Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
PU1_MinEd2Set
1 - 2500
%IB
1
1
Minimum settable operate residual current
level for step 1 in % of IBase, for 61850 Ed.2
settings
PU1_MaxEd2Set
1 - 2500
%IB
1
2500
Maximum settable operate residual current
level for step 1 in % of IBase, for 61850 Ed.2
settings
PU2_MinEd2Set
1 - 2500
%IB
1
1
Minimum settable operate residual current
level for step 2 in % of IBase, for 61850 Ed.2
settings
PU2_MaxEd2Set
1 - 2500
%IB
1
2500
Maximum settable operate residual current
level for step 2 in % of IBase, for 61850 Ed.2
settings
Table continues on next page
1MRK 511 365-UUS A
Section 8
Current protection
Phasor measurement unit RES670 2.1 ANSI
197
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...