-3V
0
=V
ref
Trip area
Instrument
transformer
angle error
3I
0
(prim)
3I
0
(to prot)
Characteristic after
angle compensation
RCAcomp
ANSI06000651-2-en.vsd
RCADir
= 0º
ANSI06000651 V2 EN
Figure 71:
Explanation of RCAComp
Directional residual power protection measuring 3I
0
· 3V
0
· cos φ
φ is defined as the angle between the residual current 3I
0
and the reference voltage (V
ref
=
-3V
0
e
-jRCA
) compensated with the set characteristic angle
RCADir
(|φ=ang(3I
0
)—
ang(V
ref
)|). The function operates when 3I
0
· 3V
0
· cos φ gets larger than the set value
SN>
. Refer to the simplified logical diagram in Figure
For trip, the residual power 3I
0
· 3V
0
· cos φ, the residual current 3I
0
and the release
voltage 3V
0
, shall be larger than the set levels (
SN_PU
,
INRelPU
and
VNRelPU
).
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function picks up, binary output signals PICKUP and PUDIRIN are activated.
If the output signals PICKUP and PUDIRIN remain active for the set delay
tDef
or after
Section 8
1MRK 511 365-UUS A
Current protection
236
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...