change with time and is mainly a function of the internal induced voltages at both ends of
the equivalent two-machine system, that is, at points SE and RE.
Measurement of the magnitude, direction and rate-of-change of load impedance relative
to a generator’s terminals provides a convenient and generally reliable means of detecting
whether machines are out-of-step and pole-slipping is taking place. Measurement of the
rotor (power) angle δ is important as well.
Rotor (power) angle δ can be thought of as the angle between the two lines, connecting
point 0 in Figure
, that is, Z(R, X) under normal load, with the points SE and RE,
respectively. These two lines are not shown in Figure
. Normal values of the power
angle, that is, under stable, steady-state, load conditions, are from 30 to 60 electrical
degrees. It can be observed in Figure
that the angle reaches 180 degrees when the
complex impedance Z(R, X) crosses the impedance line SE – RE. It then changes the sign,
and continues from -180 degrees to 0 degrees, and so on. Figure
(power) angle and the magnitude of Z(R, X) against time for the case from Figure
0
200
400
600
800
1000
1200
1400
-4
-3
-2
-1
0
1
2
3
4
Time in millis econds
®
Im
pe
da
nc
e
Z
in
O
hm
a
nd
r
ot
or
a
ng
le
in
r
ad
ia
n
®
|Z| in Ohms
angle in rad
normal
load
fault 500 ms
Z(R,X) cros s e d
the im pe da nce line , Z-line ,
conne cting points S E - RE
fault
occurrs
Z(R, X) under fault lies
on the impedance line
or near (for 3-ph faults )
Unde r 3-pha s e fa ult
condition rotor a ngle
of a pp. ±180 de gre e s
is m e a s ure d ...
rotor (power)
angle
|Z|
IEC10000110-2-en.vsd
1
2
3
1
0
IEC10000110 V2 EN
Figure 42:
Rotor (power) angle and magnitude of the complex impedance Z(R, X)
against the time
In order to be able to fully understand the principles of OOSPPAM (78), a stable case, that
is, a case where the disturbance does not make a generator to go out-of-step, must be
shown.
Section 7
1MRK 511 365-UUS A
Impedance protection
160
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...