shows both instances of ANALOGREPORT function blocks. The instance
number is visible in the bottom of each function block. For each instance, there are three
separate ANALOGREPORT blocks capable of reporting up to 24 Analog signals (8
Analog signals in each ANALOGREPORT block). These can include for example
transfer of active and reactive power or reporting the milliampere input signals to the PDC
clients as defined in IEEE C37.118 data frame format.
IEC140000120 V1 EN
Figure 32:
Multiple instances of ANALOGREPORT blocks
shows both instances of BINARYREPORT function blocks. The instance
number is visible in the bottom of each function block. For each instance, there are three
separate BINARYREPORT blocks capable of reporting up to 24 Binary signals (8 Binary
signals in each BINARYREPORT block). These binary signals can be for example dis-
connector or breaker position indications or internal/external protection alarm signals.
Section 6
1MRK 511 365-UUS A
Wide area measurement system
112
Phasor measurement unit RES670 2.1 ANSI
Technical manual