Operating and  
Installation Instructions 

Ultrasonic heat and cold meter 
Q heat 5.5 US 

– comp.

 

 

 

 

QUNDIS 

 

 

01.09.2019 

 

Note: 

In  the  text  below,  the  term  meter  refers  both  to 

the  heat  meter  and  to  the  cooling  meter  and  the  com-
bined  heat  and  cooling  meter,  unless  otherwise  speci-
fied. 

1. 

General 

1.1 

Use 

The  meter  is  used  for  heating  or  cooling  consumption  meas-
urement in systems with water.  
The meter consists of a high-tech plastic volume measurement 
unit, two temperature sensors connected in a fixed position and 
an electronic unit that calculates the energy consumption from 
the volume and temperature difference.  
The  meter  combines  modern  microcomputer  technology  with 
innovative  ultrasonic  measuring  technology  for  which  no  me-
chanically moving parts are necessary. 
This  technology  is  thus  wear  free,  robust  and  largely  mainte-
nance  free.  High  precision  and  long-term  stability  guarantee 
precise and equitable cost accounts. 

 

Note:

  The  meter  cannot  be  opened  without  damaging 

the security seal. 

1.2 

General notes 

The meter left the factory in a faultless condition where safety 
is  concerned.  The  manufacturer  will  provide  additional  tech-
nical support on request. Calibration relevant security seals on 
the  meter  must  not  be  damaged  or  removed.  Otherwise,  the 
warranty  and  calibration  validity  of  the  meter  will  no  longer 
apply. 

 

Keep the packaging so that you can transport the meter in 
its original packaging following expiry of the calibration va-
lidity. 

 

Lay all cables at a minimum distance of 500 mm to high 
voltage and high frequency cables.  

 

A relative humidity of <93% at 25 °C is permissible (without 
condensation). 

 

Avoid cavitation in the whole system due to overpressure 
i.e. at least 1 bar at qp and approx. 2 bar at qs (applies for 
approx. 80 °C). 

2. 

Safety Information 

 

The  meters  may  only  be  used  in  building  service 
engineering  plants  and  only  for  the  applications  de-
scribed. 

 

The  local  regulations  (installation  etc.)  must  be  ad-
hered to. 

 

The  operating  conditions  according  to  the  type  plate 
must  be  complied  with  during  use.  Non-compliance 
can result in hazardous situations and the expiry of all 
claims arising from liability for defects as well as liabil-
ity on the basis of any expressly granted guarantees. 

 

Do not under any circumstances carrying out welding, 
drilling or soldering work close to the meter.

 

 

The  meter  is  only  suitable  for  circulating  water  in 
heating systems.

 

 

The meter is not suitable for drinking water.

 

 

Requirements  for  circulating  water  (CEN  /  TR  16911: 
2016).

 

 

Only  personnel,  trained  in  the  installation  and  opera-
tion  of  meters  in  heating  and  cooling  systems,  may 
install and remove the meter.

 

 

Only  install  or  remove  the  meter  when  the  pipes  are 
pressure-less.

 

 

After  installing  the  meter,  check  the  leak-tightness  of 
the system.

 

 

Warranty  and  calibration  validity  will  lapse  if  the  cali-
bration relevant security seal is broken.

 

 

Only  clean  the  meter  from  outside  with  a  soft,  lightly 
wetted cloth. Do not use any spirit or cleaning solvent.

 

 

As  far  as  disposal  is  concerned,  the  meter  is  a  waste 
electronic  appliance  in  the  sense  of  European  Di-
rective  2012/19/EU  (WEEE)  and  it  must  not  be  dis-
posed of as domestic waste. 

 

The meter contains lithium batteries. Do not dispose of 
the  meter  and  the  batteries  with  domestic  waste. 
Observe the local stipulations and laws on disposal. 

 

You can return the lithium batteries to the manufactur-
er  for  appropriate  disposal  following  use.  When  ship-
ping  please  observe  legal  regulations,  in  particular, 
those  governing  the  labelling  and  packaging  of  haz-
ardous goods.

 

 

Do  not  open  the  batteries.  Do  not  bring  batteries  into 
contact  with  water  or  expose  to  temperatures  above 
80 °C.

 

 

The  meter  does  not  have  any  lightning  protection. 
Ensure  lightning  protection  via  the  in-house  installa-
tion.

 

3. 

Installation 

To install the meter proceed as follows: 

 

Determine the place of installation in line with the inscrip-
tion on the meter. 

 

Note:

  At  a 

heating  meter

 

  or  combined 

heat/cold  meter  the  mounting  place  of  the  flow  sen-

sor  cold  side  is  equivalent  to  return 

.  The 

mounting place of the flow sensor hot side is equiva-

lent to flow 

 

Note: 

At  a 

cooling  meter

 

  the  mounting  place 

of the flow sensor hot side is equivalent to the return 

.  The  mounting  place  of  the  flow  sensor  cold 

side is equivalent to flow 

 

Note: 

At  a  meter  with  an 

adjustable  mounting 

place

 

, the mounting place hot side is displayed 

as 

.  The  mounting  place  cold  side  is  dis-

played as 

 

Observe the dimensions of the meter and check whether 
there is sufficient space available. Rinse the system thor-
oughly before installing the meter. 

 