Name
Values (Range)
Unit
Step
Default
Description
VMagComp30
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate voltage at 30% of
Vn
VMagComp100
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate voltage at 100%
of Vn
IMagComp5
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate current at 5% of In
IMagComp30
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate current at 30% of
In
IMagComp100
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate current at 100%
of In
IAngComp5
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 5% of In
IAngComp30
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 30% of In
IAngComp100
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 100% of In
Table 391:
CMMXU Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
IA_DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Operation
Disabled
Enabled
-
-
Disabled
Disbled/Enabled operation
IA_Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
IA_RepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
IA_AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
IB_DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
IB_Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
IB_RepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
IB_AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
IC_DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
IC_Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
IC_RepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
IC_AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Section 16
1MRK 511 365-UUS A
Monitoring
494
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...