AMBTEMP
REAL
0
Ambient temperature from external temperature sensor
SENSFLT
BOOLEAN
0
Validity status of ambient temperature sensor
RESET
BOOLEAN
0
Reset of internal thermal load counter
Table 124:
LCPTTR (26) Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
BFI_3P
BOOLEAN
Pickup Signal
ALARM
BOOLEAN
Alarm signal
LOCKOUT
BOOLEAN
Lockout signal
Table 125:
LFPTTR (26) Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
BFI_3P
BOOLEAN
Pickup Signal
ALARM
BOOLEAN
Alarm signal
LOCKOUT
BOOLEAN
Lockout signal
8.5.5
Settings
Table 126:
LCPTTR (26) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
TRef
0 - 300
Deg C
1
90
Final temperature rise above ambient of the
line when loaded with IRef
IRef
0 - 400
%IB
1
100
The load current (in % of IBase) leading to TRef
temperature
IMult
1 - 5
-
1
1
Current multiplier when function is used for two
or more lines
Tau
1 - 1000
Min
1
45
Time constant of the line in minutes.
AlarmTemp
0 - 200
Deg C
1
80
Temperature level for pickup (alarm)
TripTemp
0 - 300
Deg C
1
90
Temperature level for trip
ReclTemp
0 - 300
Deg C
1
75
Temperature for reset of lockout after trip
tPulse
0.05 - 0.30
s
0.01
0.10
Operate pulse length. Minimum one execution
cycle
Table continues on next page
1MRK 511 365-UUS A
Section 8
Current protection
Phasor measurement unit RES670 2.1 ANSI
243
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...