18.7.14.3
Function block
IEC10000286-1-en.vsd
I103POSCMD
BLOCK
POSITION
SELECT
IEC10000286 V1 EN
Figure 255:
I103POSCMD function block
18.7.14.4
Signals
Table 535:
I103POSCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of command
POSITION
INTEGER
0
Position of controllable object
SELECT
BOOLEAN
0
Select of controllable object
18.7.14.5
Settings
Table 536:
I103POSCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type
InfNo
160 - 236
-
4
160
Information number for command output
18.7.15
Operation principle
18.7.15.1
General
IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial
communication exchanging information with a control system, and with a data transfer
rate up to 38400 bit/s. In IEC terminology, a primary station is a master and a secondary
station is a slave. The communication is based on a point-to-point principle. The master
must have software that can interpret IEC 60870-5-103 communication messages.
Introduction to IEC 60870–5–103 protocol
IEC 60870-5-103 protocol functionality consists of the following functions:
•
Event handling
•
Report of analog service values (measurements)
•
Fault location
1MRK 511 365-UUS A
Section 18
Station communication
Phasor measurement unit RES670 2.1 ANSI
661
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...