PSTO input. If any operation is allowed the signal INTONE from the Fixed signal
function block can be connected. SLGAPC function block has also an integer value
output, that generates the actual position number. The positions and the block names are
fully settable by the user. These names will appear in the menu, so the user can see the
position names instead of a number.
14.1.7.1
Graphical display
There are two possibilities for SLGAPC
•
if it is used just for the monitoring, the switches will be listed with their actual position
names, as defined by the user (max. 13 characters).
•
if it is used for control, the switches will be listed with their actual positions, but only
the first three letters of the name will be used.
In both cases, the switch full name will be shown, but the user has to redefine it when
building the Graphical Display Editor, under the "Caption". If used for the control, the
following sequence of commands will ensure:
1MRK 511 365-UUS A
Section 14
Control
Phasor measurement unit RES670 2.1 ANSI
381
Technical manual