16.10.5
Settings
Table 453:
TEILGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
tAlarm
1.0 - 99999.9
Hour
0.1
90000.0
Time limit for alarm supervision
tWarning
1.0 - 99999.9
Hour
0.1
50000.0
Time limit for warning supervision
tAddToTime
0.0 - 99999.9
Hour
0.1
0.0
Time to add to the accumulation
16.10.6
Operation principle
Figure
describes the simplified logic of the function.
Time Accumulation
Transgression Supervision
Plus Retain
BLOCK
ACC_HOUR
RESET
IN
tAlarm
OVERFLOW
WARNING
ALARM
IEC15000322.vsd
Loop Delay
Loop Delay
tWarning
ACC_DAY
ADDTIME
tAddToTime
IEC15000322 V1 EN
Figure 224:
TEILGAPC Simplified logic
TEILGAPC main functionalities
•
IN: Accumulation of the elapsed time when input IN is high