16.9.8
Technical data
Table 450:
L4UFCNTtechnical data
Function
Range or value
Accuracy
Counter value
0-65535
-
Max. count up speed
30 pulses/s (50% duty cycle)
-
16.10
Running hour-meter TEILGAPC
16.10.1
Identification
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Running hour-meter
TEILGAPC
-
-
16.10.2
Functionality
The Running hour-meter (TEILGAPC) function is a function that accumulates the elapsed
time when a given binary signal has been high, see also figure
Time Accumulation
with Retain
BLOCK
ACC_HOUR
RESET
IN
tWarning
tAlarm
OVERFLOW
WARNING
ALARM
q
-1
a>b
a
b
a>b
a
b
a>b
a
b
&
&
&
q
-1
= unit delay
IEC15000321-1-en.vsd
ACC_DAY
99 999.9 h
tAddToTime
ADDTIME
IEC15000321 V1 EN
Figure 222:
TEILGAPC logics
The main features of TEILGAPC are:
1MRK 511 365-UUS A
Section 16
Monitoring
Phasor measurement unit RES670 2.1 ANSI
579