IPOS1
IPOS2
Name of displayed string Default string value
0
0
PosUndefined
P00
1
0
Position1
P01
0
1
Position2
P10
1
1
PosBadState
P11
14.3
Generic communication function for Double Point
indication DPGAPC
14.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Generic communication function for
Double Point indication
DPGAPC
-
-
14.3.2
Functionality
Generic communication function for Double Point indication DPGAPC function block is
used to send double indications to other systems, equipment or functions in the substation
through IEC 61850-8-1 or other communication protocols. It is especially used in the
interlocking station-wide logics.
14.3.3
Function block
IEC13000081 V1 EN
Figure 135:
DPGAPC function block
1MRK 511 365-UUS A
Section 14
Control
Phasor measurement unit RES670 2.1 ANSI
385
Technical manual